Motorized Liquid Cooling Ball Valve
www.likvchina.com
Motorized Liquid Cooling Ball Valve
Remote on-off branch control with DCIM / BMS integration
The LIKE motorized liquid cooling ball valve pairs a stainless steel ball valve with an integrated electric actuator for remote on-off control and DCIM / BMS monitoring — automatic branch isolation across large liquid-cooled data halls without manual access.
At a Glance
Key Specifications
| Series | Motorized Ball Valve |
| Bore | DN15 – DN50 (1/2" – 2") |
| Actuator | Integrated electric actuator (on-off / modulating) |
| Control Signal | Dry contact on-off / 4–20 mA modulating |
| Body Material | CF8 (304) / CF8M (316L) stainless steel |
| Typical Use | Automatic cabinet branch switching / remote CDU isolation |
Note: listed specifications cover standard configurations; customization is available for specific operating conditions.
Product Overview
Built for Automated Liquid Cooling Duty
The LIKE motorized liquid cooling ball valve is an electric on-off valve developed for automated liquid cooling operation. A stainless steel ball valve on a high-platform body accepts a direct-mount electric actuator and receives open/close commands from DCIM, BMS or higher-level control systems, switching cabinet branches and CDU inlets remotely. No technician access to the rack is required: open/closed feedback signals report valve status to the monitoring platform in real time, and a manual override handwheel covers power-loss operation. The full-bore, polished flow passage suits deionized water and glycol coolants — built for large, minimally staffed cooling plants running centralized control.
Technical Data
Technical Specifications
| Parameter | Specification | Remarks |
|---|---|---|
| Size Range | DN15 / DN20 / DN25 / DN32 / DN40 / DN50 (1/2" – 2") | Other sizes on request |
| Actuator | On-off (ON-OFF) or modulating type | Selected per control duty |
| Power Supply | AC220V / AC380V / DC24V | Specify when ordering |
| Control Signal | Dry contact (on-off); 4–20 mA / 0–10 V (modulating) | Open / close feedback included |
| Stroke Time | Approx. 15 – 30 s (full stroke, by bore size) | Fast-stroke option available |
| Working Pressure | 0 – 2.0 MPa | For higher pressure, contact us |
| Temperature Range | –10 °C to +150 °C | Depends on seal selection |
| Media | Deionized water / glycol solution / synthetic coolant | Corrosion-inhibited coolants |
Selection Guide
Actuator Selection
| Type | Signal & Trait | Typical Duty |
|---|---|---|
| ON-OFF | Dry contact control with open / close feedback output | Branch switching with DCIM interlock |
| Modulating | 4–20 mA input, continuous positioning with valve position feedback | Continuous modulation with feedback |
| Manual Override | Handwheel operation on power loss, full open / close | On-site override during power loss |
Note: actuators are IP65 as standard; IP67 and explosion-proof (Ex d IIB T4) available on request.
Materials
Materials & Properties
| Part | Material | Feature |
|---|---|---|
| Body | CF8 (304) / CF8M (316L) | Full-bore corrosion-resistant casting |
| Ball | Polished stainless steel | Polished bore, smooth operation |
| Seat | PTFE | Low-torque, self-lubricating seal |
| Stem | Blow-out proof stainless steel | Shoulder-retained under pressure |
| Actuator Housing | Die-cast aluminum + epoxy coating | IP65 protection for plant environments |
| O-ring | FKM / EPDM (optional) | Selected per coolant formulation |
Design
Structural Features
01Direct-Mount Design
ISO 5211 direct-mount actuator on a high-platform body, delivered as a ready-to-wire assembly.
02Remote Central Control
Central on-off command over hundreds of branch valves via DCIM / BMS.
03Live Position Feedback
Open / closed feedback reports valve status to the platform in real time.
04Power-loss Override
Manual handwheel keeps operation available during power loss.
05Polished Low-leach Bore
Polished flow bore suits long-term DI water / glycol circulation.
06Full Bore
Full-bore passage minimizes pressure drop and pump power.
Dimensions
Connection & Dimension Reference
| Size | Actuator | End Connection | Matching Pipe |
|---|---|---|---|
| DN15 (1/2") – DN25 (1") | On-off / modulating | Internal thread / clamp / weld | Stainless tube + fittings |
| DN32 (1-1/4") – DN50 (2") | On-off / modulating | Flange / thread / weld | Stainless tube + flanges |
Note: outline and connection dimensions are subject to factory drawings; special end connections available on request.
Applications
Where It Works
Cabinet Branch Automation
Automatic branch switching by load and patrol schedule — no manual rack access needed.
Remote CDU Isolation
Remotely isolate CDU inlets / outlets to shorten maintenance windows.
Grouped Patrol Isolation
Cycle branches in groups for coolant sampling and filter changes.
Energy Storage & Power Electronics
Automated cut-in / cut-off in PCS and power module cooling circuits.
Quality
Crafted in Detail
Real product photos — what you see is what ships.
Field Guide
Installation & Maintenance
- 01Verify the actuator power supply, signal type and flow direction before installation, and check the flow arrow on the body against the piping.
- 02Leave wiring space for the actuator and dry-cycle it first to confirm end positions and feedback signals.
- 03During commissioning, command each valve from the platform and confirm the reported status matches the actual position.
- 04Avoid manual intervention while the system is pressurized; depressurize first if override is required.
- 05Periodically inspect actuator seals and the terminal box; keep the stem area free of coolant crystallization.
Ordering
How to Order
When ordering, please specify: size (DN15 – DN50), actuator type (on-off / modulating), power supply (AC220V / AC380V / DC24V), control signal (dry contact / 4–20 mA), body material (304 / 316L), end connection (thread / clamp / flange / weld), working pressure and media. Bulk supply and pre-wired harnesses are available for projects.
Liquid Cooling Valves · Fluid Control Solutions for AI Data Centers
www.likevalves.com · www.likvchina.com